Switch for alternating between outlets












2














I'm installing a Tesla charger, but I also want to install a NEMA 14-50 outlet so other EV owners can charge in that spot as well, but as it's one spot, both won't be used at the same time. I don't want to have to run two independent lines when only one will be in use at a time. Is there something I could use that would take one line input, and output two separate lines with a toggle switch determining which one is active? And even if so, would such a thing be within code?










share|improve this question







New contributor




directedition is a new contributor to this site. Take care in asking for clarification, commenting, and answering.
Check out our Code of Conduct.




















  • What size breaker and wire is required for a Tesla home charger? Do Tesla chargers come with a NEMA 14-50 plug or are they hard wired?
    – Jim Stewart
    Dec 28 '18 at 17:05






  • 3




    When the chart says "55A @60C", you are allowed to round up to 60. 6 is my breakover point for switching for aluminum, so I would use 6Cu or 4Al depending on cost. You don't get any brownie points for using copper, the fear associated with aluminum is totally inapplicable to both modern wire and large wire at these feeder sizes.
    – Harper
    Dec 28 '18 at 18:18








  • 2




    Indeed, and Tesla themselves recommend 80% for people who charge up daily. I have a Model 3, which by far has their most stable batteries, the 2170s. At 80% You can expect around 5% degradation at 50k miles and 10% at 150k miles. With available data, it's projected 20% degradation at around 500k miles. Warranty will replace the battery at 30% (that is, 70% remaining). Charging to 90% will have an impact, but I find the projected losses acceptable.
    – directedition
    Dec 28 '18 at 19:03








  • 3




    If I recall a news story correctly, Tesla flashed a software update to everyone in Florida right before the hurricane, telling their chargers to top the battery to 100% and allowing cars to discharge much deeper than is normally allowed under terms of sale, i.e. If you didn't pay for an extended range battery they enabled that DoD anyway.
    – Harper
    Dec 28 '18 at 19:24








  • 1




    @JimStewart You can set the amperage on the Tesla charger, but that requires dissembling the unit (exposing hot wires, meaning you'll want to switch off the breaker). So in any practical sense you would set it once and leave it, which largely defeats the purpose of installing a Level 2 charger.
    – directedition
    2 days ago
















2














I'm installing a Tesla charger, but I also want to install a NEMA 14-50 outlet so other EV owners can charge in that spot as well, but as it's one spot, both won't be used at the same time. I don't want to have to run two independent lines when only one will be in use at a time. Is there something I could use that would take one line input, and output two separate lines with a toggle switch determining which one is active? And even if so, would such a thing be within code?










share|improve this question







New contributor




directedition is a new contributor to this site. Take care in asking for clarification, commenting, and answering.
Check out our Code of Conduct.




















  • What size breaker and wire is required for a Tesla home charger? Do Tesla chargers come with a NEMA 14-50 plug or are they hard wired?
    – Jim Stewart
    Dec 28 '18 at 17:05






  • 3




    When the chart says "55A @60C", you are allowed to round up to 60. 6 is my breakover point for switching for aluminum, so I would use 6Cu or 4Al depending on cost. You don't get any brownie points for using copper, the fear associated with aluminum is totally inapplicable to both modern wire and large wire at these feeder sizes.
    – Harper
    Dec 28 '18 at 18:18








  • 2




    Indeed, and Tesla themselves recommend 80% for people who charge up daily. I have a Model 3, which by far has their most stable batteries, the 2170s. At 80% You can expect around 5% degradation at 50k miles and 10% at 150k miles. With available data, it's projected 20% degradation at around 500k miles. Warranty will replace the battery at 30% (that is, 70% remaining). Charging to 90% will have an impact, but I find the projected losses acceptable.
    – directedition
    Dec 28 '18 at 19:03








  • 3




    If I recall a news story correctly, Tesla flashed a software update to everyone in Florida right before the hurricane, telling their chargers to top the battery to 100% and allowing cars to discharge much deeper than is normally allowed under terms of sale, i.e. If you didn't pay for an extended range battery they enabled that DoD anyway.
    – Harper
    Dec 28 '18 at 19:24








  • 1




    @JimStewart You can set the amperage on the Tesla charger, but that requires dissembling the unit (exposing hot wires, meaning you'll want to switch off the breaker). So in any practical sense you would set it once and leave it, which largely defeats the purpose of installing a Level 2 charger.
    – directedition
    2 days ago














2












2








2







I'm installing a Tesla charger, but I also want to install a NEMA 14-50 outlet so other EV owners can charge in that spot as well, but as it's one spot, both won't be used at the same time. I don't want to have to run two independent lines when only one will be in use at a time. Is there something I could use that would take one line input, and output two separate lines with a toggle switch determining which one is active? And even if so, would such a thing be within code?










share|improve this question







New contributor




directedition is a new contributor to this site. Take care in asking for clarification, commenting, and answering.
Check out our Code of Conduct.











I'm installing a Tesla charger, but I also want to install a NEMA 14-50 outlet so other EV owners can charge in that spot as well, but as it's one spot, both won't be used at the same time. I don't want to have to run two independent lines when only one will be in use at a time. Is there something I could use that would take one line input, and output two separate lines with a toggle switch determining which one is active? And even if so, would such a thing be within code?







electrical electric-vehicle






share|improve this question







New contributor




directedition is a new contributor to this site. Take care in asking for clarification, commenting, and answering.
Check out our Code of Conduct.











share|improve this question







New contributor




directedition is a new contributor to this site. Take care in asking for clarification, commenting, and answering.
Check out our Code of Conduct.









share|improve this question




share|improve this question






New contributor




directedition is a new contributor to this site. Take care in asking for clarification, commenting, and answering.
Check out our Code of Conduct.









asked Dec 28 '18 at 15:50









directedition

1163




1163




New contributor




directedition is a new contributor to this site. Take care in asking for clarification, commenting, and answering.
Check out our Code of Conduct.





New contributor





directedition is a new contributor to this site. Take care in asking for clarification, commenting, and answering.
Check out our Code of Conduct.






directedition is a new contributor to this site. Take care in asking for clarification, commenting, and answering.
Check out our Code of Conduct.












  • What size breaker and wire is required for a Tesla home charger? Do Tesla chargers come with a NEMA 14-50 plug or are they hard wired?
    – Jim Stewart
    Dec 28 '18 at 17:05






  • 3




    When the chart says "55A @60C", you are allowed to round up to 60. 6 is my breakover point for switching for aluminum, so I would use 6Cu or 4Al depending on cost. You don't get any brownie points for using copper, the fear associated with aluminum is totally inapplicable to both modern wire and large wire at these feeder sizes.
    – Harper
    Dec 28 '18 at 18:18








  • 2




    Indeed, and Tesla themselves recommend 80% for people who charge up daily. I have a Model 3, which by far has their most stable batteries, the 2170s. At 80% You can expect around 5% degradation at 50k miles and 10% at 150k miles. With available data, it's projected 20% degradation at around 500k miles. Warranty will replace the battery at 30% (that is, 70% remaining). Charging to 90% will have an impact, but I find the projected losses acceptable.
    – directedition
    Dec 28 '18 at 19:03








  • 3




    If I recall a news story correctly, Tesla flashed a software update to everyone in Florida right before the hurricane, telling their chargers to top the battery to 100% and allowing cars to discharge much deeper than is normally allowed under terms of sale, i.e. If you didn't pay for an extended range battery they enabled that DoD anyway.
    – Harper
    Dec 28 '18 at 19:24








  • 1




    @JimStewart You can set the amperage on the Tesla charger, but that requires dissembling the unit (exposing hot wires, meaning you'll want to switch off the breaker). So in any practical sense you would set it once and leave it, which largely defeats the purpose of installing a Level 2 charger.
    – directedition
    2 days ago


















  • What size breaker and wire is required for a Tesla home charger? Do Tesla chargers come with a NEMA 14-50 plug or are they hard wired?
    – Jim Stewart
    Dec 28 '18 at 17:05






  • 3




    When the chart says "55A @60C", you are allowed to round up to 60. 6 is my breakover point for switching for aluminum, so I would use 6Cu or 4Al depending on cost. You don't get any brownie points for using copper, the fear associated with aluminum is totally inapplicable to both modern wire and large wire at these feeder sizes.
    – Harper
    Dec 28 '18 at 18:18








  • 2




    Indeed, and Tesla themselves recommend 80% for people who charge up daily. I have a Model 3, which by far has their most stable batteries, the 2170s. At 80% You can expect around 5% degradation at 50k miles and 10% at 150k miles. With available data, it's projected 20% degradation at around 500k miles. Warranty will replace the battery at 30% (that is, 70% remaining). Charging to 90% will have an impact, but I find the projected losses acceptable.
    – directedition
    Dec 28 '18 at 19:03








  • 3




    If I recall a news story correctly, Tesla flashed a software update to everyone in Florida right before the hurricane, telling their chargers to top the battery to 100% and allowing cars to discharge much deeper than is normally allowed under terms of sale, i.e. If you didn't pay for an extended range battery they enabled that DoD anyway.
    – Harper
    Dec 28 '18 at 19:24








  • 1




    @JimStewart You can set the amperage on the Tesla charger, but that requires dissembling the unit (exposing hot wires, meaning you'll want to switch off the breaker). So in any practical sense you would set it once and leave it, which largely defeats the purpose of installing a Level 2 charger.
    – directedition
    2 days ago
















What size breaker and wire is required for a Tesla home charger? Do Tesla chargers come with a NEMA 14-50 plug or are they hard wired?
– Jim Stewart
Dec 28 '18 at 17:05




What size breaker and wire is required for a Tesla home charger? Do Tesla chargers come with a NEMA 14-50 plug or are they hard wired?
– Jim Stewart
Dec 28 '18 at 17:05




3




3




When the chart says "55A @60C", you are allowed to round up to 60. 6 is my breakover point for switching for aluminum, so I would use 6Cu or 4Al depending on cost. You don't get any brownie points for using copper, the fear associated with aluminum is totally inapplicable to both modern wire and large wire at these feeder sizes.
– Harper
Dec 28 '18 at 18:18






When the chart says "55A @60C", you are allowed to round up to 60. 6 is my breakover point for switching for aluminum, so I would use 6Cu or 4Al depending on cost. You don't get any brownie points for using copper, the fear associated with aluminum is totally inapplicable to both modern wire and large wire at these feeder sizes.
– Harper
Dec 28 '18 at 18:18






2




2




Indeed, and Tesla themselves recommend 80% for people who charge up daily. I have a Model 3, which by far has their most stable batteries, the 2170s. At 80% You can expect around 5% degradation at 50k miles and 10% at 150k miles. With available data, it's projected 20% degradation at around 500k miles. Warranty will replace the battery at 30% (that is, 70% remaining). Charging to 90% will have an impact, but I find the projected losses acceptable.
– directedition
Dec 28 '18 at 19:03






Indeed, and Tesla themselves recommend 80% for people who charge up daily. I have a Model 3, which by far has their most stable batteries, the 2170s. At 80% You can expect around 5% degradation at 50k miles and 10% at 150k miles. With available data, it's projected 20% degradation at around 500k miles. Warranty will replace the battery at 30% (that is, 70% remaining). Charging to 90% will have an impact, but I find the projected losses acceptable.
– directedition
Dec 28 '18 at 19:03






3




3




If I recall a news story correctly, Tesla flashed a software update to everyone in Florida right before the hurricane, telling their chargers to top the battery to 100% and allowing cars to discharge much deeper than is normally allowed under terms of sale, i.e. If you didn't pay for an extended range battery they enabled that DoD anyway.
– Harper
Dec 28 '18 at 19:24






If I recall a news story correctly, Tesla flashed a software update to everyone in Florida right before the hurricane, telling their chargers to top the battery to 100% and allowing cars to discharge much deeper than is normally allowed under terms of sale, i.e. If you didn't pay for an extended range battery they enabled that DoD anyway.
– Harper
Dec 28 '18 at 19:24






1




1




@JimStewart You can set the amperage on the Tesla charger, but that requires dissembling the unit (exposing hot wires, meaning you'll want to switch off the breaker). So in any practical sense you would set it once and leave it, which largely defeats the purpose of installing a Level 2 charger.
– directedition
2 days ago




@JimStewart You can set the amperage on the Tesla charger, but that requires dissembling the unit (exposing hot wires, meaning you'll want to switch off the breaker). So in any practical sense you would set it once and leave it, which largely defeats the purpose of installing a Level 2 charger.
– directedition
2 days ago










2 Answers
2






active

oldest

votes


















3














To do it with a switch, you would need a DPDT switch with one throw wired to the charger, the other wired to the receptacle. The DPDT switch would need to be rated for the ampacity of the circuit, which means it's going to be BIG. For example, this GE switch would work:



GE TC35322



It might be easier to just install the receptacle, and cord and plug connect the charger.






share|improve this answer





























    9














    You are not allowed to put multiple outlets on a 50A/60A circuit. You can on a 30A, and that would've been simple, but that will slow charge.



    However, your Tesla charger wants 60A and you cannot put a 50A receptacle on a 60A circuit.



    enter image description here



    Really, the best way to do this is a subpanel. But wait.



    The keystone is a $30 interlock kit made by Siemens for its panels. This replaces the expensive, huge Frankenstein switch. The interlock kit straps between two 2-pole breakers, making it so only one can be on at a time. This is intended for generator interlocks, where the breakers are back-fed, but it's fine to normal-feed the breakers too. So your cost is




    • $30 interlock kit

    • $40 8-space, main-lug (no breaker on the sub**) panel

    • $18 two 40-60A breakers, $9 each

    • $5 ground bar


    I also got you 4 extra spaces in the panel to use as you please.



    You feed the lugs normally, you don't backfeed. The two breakers on the interlock are




    • a 60A breaker going to the Hardwired Tesla charger, full rate unthrottled

    • a 50A breaker going to the NEMA 14-50, which is the legal/right way to do that


    And honestly, I do not see a reason you can't simply forego the interlock and allow both outlets to be hot at the same time. The breaker in the main panel protects the wiring to the subpanel and the subpanel itself (which is rated 125A), and the individual breakers protect the wiring to the equipment. If you try to charge two cars at once without rate throttling, yeah, you'll trip the breaker downstairs.



    The feed from the main panel to this subpanel can be any size of wire you please, as long as the breaker in the main panel protects the wire. At these sizes, there are no brownie points for using copper*, so consider aluminum wire/cable. For 60A feeder, use #6Cu or #4Al. For 100A feeder, #3Cu or #1Al at which point you definitely don't need the interlock. (You're allowed to oversubscribe a panel and this won't matter).



    * Aluminum feeder does not have the problem that 1970s branch circuits had. The metal conducts 12x better per dollar. This is why it is widely used on feeder, where the mineral value becomes a significant part of cable cost.



    ** because it's not needed in subpanels in the same building, a breaker is needed in the main panel to feed/protect the cable run. Getting the subpanel main to pop before the feed breaker doesn't work, without deep-diving into SCADA tech.






    share|improve this answer























    • Just curious, not familiar with US electrical code: Would wiring an extra 50A breaker in series with the 50A socket on the 60A circuit make it OK?
      – rackandboneman
      Dec 28 '18 at 19:24






    • 1




      I'd imagine not wanting to risk tripping the house breaker by trying to charge 2 cars at once would be the motivation for wanting an interlock to only power on charger at a time. That goal should still be possible without an interlock though, just use a smaller sub-panel so that the subpanel's main breaker trips if both chargers go live simultaneously.
      – Dan Neely
      Dec 28 '18 at 20:04






    • 2




      @DanNeely doesn't work, because you still need to protect the wire to the subpanel with a ~60A breaker in the main panel. It is impossible to "sequence" breakers, i.e. Get the more convenient one to trip first. In an outbuilding for instance, Murphy's Law requires the breaker in the other building to trip anytime it is raining.
      – Harper
      Dec 28 '18 at 20:14








    • 1




      @DanNeely -- selective coordination of circuit breakers is a tricky business at best that is generally unsupported for light-duty panelboard breakers.
      – ThreePhaseEel
      Dec 28 '18 at 22:12






    • 1




      Since EV owners are likely to have guests with EVs and some EV chargers use a NEMA 6-50 whereas others evidently use a NEMA 14-50, the subpanel approach of @Harper would allow having a TESLA charger hardwired for the resident and would allow installation of both a NEMA 6-50R and a NEMA 14-50R to accommodate any EV charger. Although I gather there are adaptors to allow a NEMA 6-50P to connect to a NEMA 14-50R so all that is needed is a 14-50R.
      – Jim Stewart
      yesterday













    Your Answer








    StackExchange.ready(function() {
    var channelOptions = {
    tags: "".split(" "),
    id: "73"
    };
    initTagRenderer("".split(" "), "".split(" "), channelOptions);

    StackExchange.using("externalEditor", function() {
    // Have to fire editor after snippets, if snippets enabled
    if (StackExchange.settings.snippets.snippetsEnabled) {
    StackExchange.using("snippets", function() {
    createEditor();
    });
    }
    else {
    createEditor();
    }
    });

    function createEditor() {
    StackExchange.prepareEditor({
    heartbeatType: 'answer',
    autoActivateHeartbeat: false,
    convertImagesToLinks: false,
    noModals: true,
    showLowRepImageUploadWarning: true,
    reputationToPostImages: null,
    bindNavPrevention: true,
    postfix: "",
    imageUploader: {
    brandingHtml: "Powered by u003ca class="icon-imgur-white" href="https://imgur.com/"u003eu003c/au003e",
    contentPolicyHtml: "User contributions licensed under u003ca href="https://creativecommons.org/licenses/by-sa/3.0/"u003ecc by-sa 3.0 with attribution requiredu003c/au003e u003ca href="https://stackoverflow.com/legal/content-policy"u003e(content policy)u003c/au003e",
    allowUrls: true
    },
    noCode: true, onDemand: true,
    discardSelector: ".discard-answer"
    ,immediatelyShowMarkdownHelp:true
    });


    }
    });






    directedition is a new contributor. Be nice, and check out our Code of Conduct.










    draft saved

    draft discarded


















    StackExchange.ready(
    function () {
    StackExchange.openid.initPostLogin('.new-post-login', 'https%3a%2f%2fdiy.stackexchange.com%2fquestions%2f153571%2fswitch-for-alternating-between-outlets%23new-answer', 'question_page');
    }
    );

    Post as a guest















    Required, but never shown

























    2 Answers
    2






    active

    oldest

    votes








    2 Answers
    2






    active

    oldest

    votes









    active

    oldest

    votes






    active

    oldest

    votes









    3














    To do it with a switch, you would need a DPDT switch with one throw wired to the charger, the other wired to the receptacle. The DPDT switch would need to be rated for the ampacity of the circuit, which means it's going to be BIG. For example, this GE switch would work:



    GE TC35322



    It might be easier to just install the receptacle, and cord and plug connect the charger.






    share|improve this answer


























      3














      To do it with a switch, you would need a DPDT switch with one throw wired to the charger, the other wired to the receptacle. The DPDT switch would need to be rated for the ampacity of the circuit, which means it's going to be BIG. For example, this GE switch would work:



      GE TC35322



      It might be easier to just install the receptacle, and cord and plug connect the charger.






      share|improve this answer
























        3












        3








        3






        To do it with a switch, you would need a DPDT switch with one throw wired to the charger, the other wired to the receptacle. The DPDT switch would need to be rated for the ampacity of the circuit, which means it's going to be BIG. For example, this GE switch would work:



        GE TC35322



        It might be easier to just install the receptacle, and cord and plug connect the charger.






        share|improve this answer












        To do it with a switch, you would need a DPDT switch with one throw wired to the charger, the other wired to the receptacle. The DPDT switch would need to be rated for the ampacity of the circuit, which means it's going to be BIG. For example, this GE switch would work:



        GE TC35322



        It might be easier to just install the receptacle, and cord and plug connect the charger.







        share|improve this answer












        share|improve this answer



        share|improve this answer










        answered Dec 28 '18 at 16:38









        batsplatsterson

        9,59111229




        9,59111229

























            9














            You are not allowed to put multiple outlets on a 50A/60A circuit. You can on a 30A, and that would've been simple, but that will slow charge.



            However, your Tesla charger wants 60A and you cannot put a 50A receptacle on a 60A circuit.



            enter image description here



            Really, the best way to do this is a subpanel. But wait.



            The keystone is a $30 interlock kit made by Siemens for its panels. This replaces the expensive, huge Frankenstein switch. The interlock kit straps between two 2-pole breakers, making it so only one can be on at a time. This is intended for generator interlocks, where the breakers are back-fed, but it's fine to normal-feed the breakers too. So your cost is




            • $30 interlock kit

            • $40 8-space, main-lug (no breaker on the sub**) panel

            • $18 two 40-60A breakers, $9 each

            • $5 ground bar


            I also got you 4 extra spaces in the panel to use as you please.



            You feed the lugs normally, you don't backfeed. The two breakers on the interlock are




            • a 60A breaker going to the Hardwired Tesla charger, full rate unthrottled

            • a 50A breaker going to the NEMA 14-50, which is the legal/right way to do that


            And honestly, I do not see a reason you can't simply forego the interlock and allow both outlets to be hot at the same time. The breaker in the main panel protects the wiring to the subpanel and the subpanel itself (which is rated 125A), and the individual breakers protect the wiring to the equipment. If you try to charge two cars at once without rate throttling, yeah, you'll trip the breaker downstairs.



            The feed from the main panel to this subpanel can be any size of wire you please, as long as the breaker in the main panel protects the wire. At these sizes, there are no brownie points for using copper*, so consider aluminum wire/cable. For 60A feeder, use #6Cu or #4Al. For 100A feeder, #3Cu or #1Al at which point you definitely don't need the interlock. (You're allowed to oversubscribe a panel and this won't matter).



            * Aluminum feeder does not have the problem that 1970s branch circuits had. The metal conducts 12x better per dollar. This is why it is widely used on feeder, where the mineral value becomes a significant part of cable cost.



            ** because it's not needed in subpanels in the same building, a breaker is needed in the main panel to feed/protect the cable run. Getting the subpanel main to pop before the feed breaker doesn't work, without deep-diving into SCADA tech.






            share|improve this answer























            • Just curious, not familiar with US electrical code: Would wiring an extra 50A breaker in series with the 50A socket on the 60A circuit make it OK?
              – rackandboneman
              Dec 28 '18 at 19:24






            • 1




              I'd imagine not wanting to risk tripping the house breaker by trying to charge 2 cars at once would be the motivation for wanting an interlock to only power on charger at a time. That goal should still be possible without an interlock though, just use a smaller sub-panel so that the subpanel's main breaker trips if both chargers go live simultaneously.
              – Dan Neely
              Dec 28 '18 at 20:04






            • 2




              @DanNeely doesn't work, because you still need to protect the wire to the subpanel with a ~60A breaker in the main panel. It is impossible to "sequence" breakers, i.e. Get the more convenient one to trip first. In an outbuilding for instance, Murphy's Law requires the breaker in the other building to trip anytime it is raining.
              – Harper
              Dec 28 '18 at 20:14








            • 1




              @DanNeely -- selective coordination of circuit breakers is a tricky business at best that is generally unsupported for light-duty panelboard breakers.
              – ThreePhaseEel
              Dec 28 '18 at 22:12






            • 1




              Since EV owners are likely to have guests with EVs and some EV chargers use a NEMA 6-50 whereas others evidently use a NEMA 14-50, the subpanel approach of @Harper would allow having a TESLA charger hardwired for the resident and would allow installation of both a NEMA 6-50R and a NEMA 14-50R to accommodate any EV charger. Although I gather there are adaptors to allow a NEMA 6-50P to connect to a NEMA 14-50R so all that is needed is a 14-50R.
              – Jim Stewart
              yesterday


















            9














            You are not allowed to put multiple outlets on a 50A/60A circuit. You can on a 30A, and that would've been simple, but that will slow charge.



            However, your Tesla charger wants 60A and you cannot put a 50A receptacle on a 60A circuit.



            enter image description here



            Really, the best way to do this is a subpanel. But wait.



            The keystone is a $30 interlock kit made by Siemens for its panels. This replaces the expensive, huge Frankenstein switch. The interlock kit straps between two 2-pole breakers, making it so only one can be on at a time. This is intended for generator interlocks, where the breakers are back-fed, but it's fine to normal-feed the breakers too. So your cost is




            • $30 interlock kit

            • $40 8-space, main-lug (no breaker on the sub**) panel

            • $18 two 40-60A breakers, $9 each

            • $5 ground bar


            I also got you 4 extra spaces in the panel to use as you please.



            You feed the lugs normally, you don't backfeed. The two breakers on the interlock are




            • a 60A breaker going to the Hardwired Tesla charger, full rate unthrottled

            • a 50A breaker going to the NEMA 14-50, which is the legal/right way to do that


            And honestly, I do not see a reason you can't simply forego the interlock and allow both outlets to be hot at the same time. The breaker in the main panel protects the wiring to the subpanel and the subpanel itself (which is rated 125A), and the individual breakers protect the wiring to the equipment. If you try to charge two cars at once without rate throttling, yeah, you'll trip the breaker downstairs.



            The feed from the main panel to this subpanel can be any size of wire you please, as long as the breaker in the main panel protects the wire. At these sizes, there are no brownie points for using copper*, so consider aluminum wire/cable. For 60A feeder, use #6Cu or #4Al. For 100A feeder, #3Cu or #1Al at which point you definitely don't need the interlock. (You're allowed to oversubscribe a panel and this won't matter).



            * Aluminum feeder does not have the problem that 1970s branch circuits had. The metal conducts 12x better per dollar. This is why it is widely used on feeder, where the mineral value becomes a significant part of cable cost.



            ** because it's not needed in subpanels in the same building, a breaker is needed in the main panel to feed/protect the cable run. Getting the subpanel main to pop before the feed breaker doesn't work, without deep-diving into SCADA tech.






            share|improve this answer























            • Just curious, not familiar with US electrical code: Would wiring an extra 50A breaker in series with the 50A socket on the 60A circuit make it OK?
              – rackandboneman
              Dec 28 '18 at 19:24






            • 1




              I'd imagine not wanting to risk tripping the house breaker by trying to charge 2 cars at once would be the motivation for wanting an interlock to only power on charger at a time. That goal should still be possible without an interlock though, just use a smaller sub-panel so that the subpanel's main breaker trips if both chargers go live simultaneously.
              – Dan Neely
              Dec 28 '18 at 20:04






            • 2




              @DanNeely doesn't work, because you still need to protect the wire to the subpanel with a ~60A breaker in the main panel. It is impossible to "sequence" breakers, i.e. Get the more convenient one to trip first. In an outbuilding for instance, Murphy's Law requires the breaker in the other building to trip anytime it is raining.
              – Harper
              Dec 28 '18 at 20:14








            • 1




              @DanNeely -- selective coordination of circuit breakers is a tricky business at best that is generally unsupported for light-duty panelboard breakers.
              – ThreePhaseEel
              Dec 28 '18 at 22:12






            • 1




              Since EV owners are likely to have guests with EVs and some EV chargers use a NEMA 6-50 whereas others evidently use a NEMA 14-50, the subpanel approach of @Harper would allow having a TESLA charger hardwired for the resident and would allow installation of both a NEMA 6-50R and a NEMA 14-50R to accommodate any EV charger. Although I gather there are adaptors to allow a NEMA 6-50P to connect to a NEMA 14-50R so all that is needed is a 14-50R.
              – Jim Stewart
              yesterday
















            9












            9








            9






            You are not allowed to put multiple outlets on a 50A/60A circuit. You can on a 30A, and that would've been simple, but that will slow charge.



            However, your Tesla charger wants 60A and you cannot put a 50A receptacle on a 60A circuit.



            enter image description here



            Really, the best way to do this is a subpanel. But wait.



            The keystone is a $30 interlock kit made by Siemens for its panels. This replaces the expensive, huge Frankenstein switch. The interlock kit straps between two 2-pole breakers, making it so only one can be on at a time. This is intended for generator interlocks, where the breakers are back-fed, but it's fine to normal-feed the breakers too. So your cost is




            • $30 interlock kit

            • $40 8-space, main-lug (no breaker on the sub**) panel

            • $18 two 40-60A breakers, $9 each

            • $5 ground bar


            I also got you 4 extra spaces in the panel to use as you please.



            You feed the lugs normally, you don't backfeed. The two breakers on the interlock are




            • a 60A breaker going to the Hardwired Tesla charger, full rate unthrottled

            • a 50A breaker going to the NEMA 14-50, which is the legal/right way to do that


            And honestly, I do not see a reason you can't simply forego the interlock and allow both outlets to be hot at the same time. The breaker in the main panel protects the wiring to the subpanel and the subpanel itself (which is rated 125A), and the individual breakers protect the wiring to the equipment. If you try to charge two cars at once without rate throttling, yeah, you'll trip the breaker downstairs.



            The feed from the main panel to this subpanel can be any size of wire you please, as long as the breaker in the main panel protects the wire. At these sizes, there are no brownie points for using copper*, so consider aluminum wire/cable. For 60A feeder, use #6Cu or #4Al. For 100A feeder, #3Cu or #1Al at which point you definitely don't need the interlock. (You're allowed to oversubscribe a panel and this won't matter).



            * Aluminum feeder does not have the problem that 1970s branch circuits had. The metal conducts 12x better per dollar. This is why it is widely used on feeder, where the mineral value becomes a significant part of cable cost.



            ** because it's not needed in subpanels in the same building, a breaker is needed in the main panel to feed/protect the cable run. Getting the subpanel main to pop before the feed breaker doesn't work, without deep-diving into SCADA tech.






            share|improve this answer














            You are not allowed to put multiple outlets on a 50A/60A circuit. You can on a 30A, and that would've been simple, but that will slow charge.



            However, your Tesla charger wants 60A and you cannot put a 50A receptacle on a 60A circuit.



            enter image description here



            Really, the best way to do this is a subpanel. But wait.



            The keystone is a $30 interlock kit made by Siemens for its panels. This replaces the expensive, huge Frankenstein switch. The interlock kit straps between two 2-pole breakers, making it so only one can be on at a time. This is intended for generator interlocks, where the breakers are back-fed, but it's fine to normal-feed the breakers too. So your cost is




            • $30 interlock kit

            • $40 8-space, main-lug (no breaker on the sub**) panel

            • $18 two 40-60A breakers, $9 each

            • $5 ground bar


            I also got you 4 extra spaces in the panel to use as you please.



            You feed the lugs normally, you don't backfeed. The two breakers on the interlock are




            • a 60A breaker going to the Hardwired Tesla charger, full rate unthrottled

            • a 50A breaker going to the NEMA 14-50, which is the legal/right way to do that


            And honestly, I do not see a reason you can't simply forego the interlock and allow both outlets to be hot at the same time. The breaker in the main panel protects the wiring to the subpanel and the subpanel itself (which is rated 125A), and the individual breakers protect the wiring to the equipment. If you try to charge two cars at once without rate throttling, yeah, you'll trip the breaker downstairs.



            The feed from the main panel to this subpanel can be any size of wire you please, as long as the breaker in the main panel protects the wire. At these sizes, there are no brownie points for using copper*, so consider aluminum wire/cable. For 60A feeder, use #6Cu or #4Al. For 100A feeder, #3Cu or #1Al at which point you definitely don't need the interlock. (You're allowed to oversubscribe a panel and this won't matter).



            * Aluminum feeder does not have the problem that 1970s branch circuits had. The metal conducts 12x better per dollar. This is why it is widely used on feeder, where the mineral value becomes a significant part of cable cost.



            ** because it's not needed in subpanels in the same building, a breaker is needed in the main panel to feed/protect the cable run. Getting the subpanel main to pop before the feed breaker doesn't work, without deep-diving into SCADA tech.







            share|improve this answer














            share|improve this answer



            share|improve this answer








            edited Dec 29 '18 at 17:44

























            answered Dec 28 '18 at 19:19









            Harper

            65.3k342132




            65.3k342132












            • Just curious, not familiar with US electrical code: Would wiring an extra 50A breaker in series with the 50A socket on the 60A circuit make it OK?
              – rackandboneman
              Dec 28 '18 at 19:24






            • 1




              I'd imagine not wanting to risk tripping the house breaker by trying to charge 2 cars at once would be the motivation for wanting an interlock to only power on charger at a time. That goal should still be possible without an interlock though, just use a smaller sub-panel so that the subpanel's main breaker trips if both chargers go live simultaneously.
              – Dan Neely
              Dec 28 '18 at 20:04






            • 2




              @DanNeely doesn't work, because you still need to protect the wire to the subpanel with a ~60A breaker in the main panel. It is impossible to "sequence" breakers, i.e. Get the more convenient one to trip first. In an outbuilding for instance, Murphy's Law requires the breaker in the other building to trip anytime it is raining.
              – Harper
              Dec 28 '18 at 20:14








            • 1




              @DanNeely -- selective coordination of circuit breakers is a tricky business at best that is generally unsupported for light-duty panelboard breakers.
              – ThreePhaseEel
              Dec 28 '18 at 22:12






            • 1




              Since EV owners are likely to have guests with EVs and some EV chargers use a NEMA 6-50 whereas others evidently use a NEMA 14-50, the subpanel approach of @Harper would allow having a TESLA charger hardwired for the resident and would allow installation of both a NEMA 6-50R and a NEMA 14-50R to accommodate any EV charger. Although I gather there are adaptors to allow a NEMA 6-50P to connect to a NEMA 14-50R so all that is needed is a 14-50R.
              – Jim Stewart
              yesterday




















            • Just curious, not familiar with US electrical code: Would wiring an extra 50A breaker in series with the 50A socket on the 60A circuit make it OK?
              – rackandboneman
              Dec 28 '18 at 19:24






            • 1




              I'd imagine not wanting to risk tripping the house breaker by trying to charge 2 cars at once would be the motivation for wanting an interlock to only power on charger at a time. That goal should still be possible without an interlock though, just use a smaller sub-panel so that the subpanel's main breaker trips if both chargers go live simultaneously.
              – Dan Neely
              Dec 28 '18 at 20:04






            • 2




              @DanNeely doesn't work, because you still need to protect the wire to the subpanel with a ~60A breaker in the main panel. It is impossible to "sequence" breakers, i.e. Get the more convenient one to trip first. In an outbuilding for instance, Murphy's Law requires the breaker in the other building to trip anytime it is raining.
              – Harper
              Dec 28 '18 at 20:14








            • 1




              @DanNeely -- selective coordination of circuit breakers is a tricky business at best that is generally unsupported for light-duty panelboard breakers.
              – ThreePhaseEel
              Dec 28 '18 at 22:12






            • 1




              Since EV owners are likely to have guests with EVs and some EV chargers use a NEMA 6-50 whereas others evidently use a NEMA 14-50, the subpanel approach of @Harper would allow having a TESLA charger hardwired for the resident and would allow installation of both a NEMA 6-50R and a NEMA 14-50R to accommodate any EV charger. Although I gather there are adaptors to allow a NEMA 6-50P to connect to a NEMA 14-50R so all that is needed is a 14-50R.
              – Jim Stewart
              yesterday


















            Just curious, not familiar with US electrical code: Would wiring an extra 50A breaker in series with the 50A socket on the 60A circuit make it OK?
            – rackandboneman
            Dec 28 '18 at 19:24




            Just curious, not familiar with US electrical code: Would wiring an extra 50A breaker in series with the 50A socket on the 60A circuit make it OK?
            – rackandboneman
            Dec 28 '18 at 19:24




            1




            1




            I'd imagine not wanting to risk tripping the house breaker by trying to charge 2 cars at once would be the motivation for wanting an interlock to only power on charger at a time. That goal should still be possible without an interlock though, just use a smaller sub-panel so that the subpanel's main breaker trips if both chargers go live simultaneously.
            – Dan Neely
            Dec 28 '18 at 20:04




            I'd imagine not wanting to risk tripping the house breaker by trying to charge 2 cars at once would be the motivation for wanting an interlock to only power on charger at a time. That goal should still be possible without an interlock though, just use a smaller sub-panel so that the subpanel's main breaker trips if both chargers go live simultaneously.
            – Dan Neely
            Dec 28 '18 at 20:04




            2




            2




            @DanNeely doesn't work, because you still need to protect the wire to the subpanel with a ~60A breaker in the main panel. It is impossible to "sequence" breakers, i.e. Get the more convenient one to trip first. In an outbuilding for instance, Murphy's Law requires the breaker in the other building to trip anytime it is raining.
            – Harper
            Dec 28 '18 at 20:14






            @DanNeely doesn't work, because you still need to protect the wire to the subpanel with a ~60A breaker in the main panel. It is impossible to "sequence" breakers, i.e. Get the more convenient one to trip first. In an outbuilding for instance, Murphy's Law requires the breaker in the other building to trip anytime it is raining.
            – Harper
            Dec 28 '18 at 20:14






            1




            1




            @DanNeely -- selective coordination of circuit breakers is a tricky business at best that is generally unsupported for light-duty panelboard breakers.
            – ThreePhaseEel
            Dec 28 '18 at 22:12




            @DanNeely -- selective coordination of circuit breakers is a tricky business at best that is generally unsupported for light-duty panelboard breakers.
            – ThreePhaseEel
            Dec 28 '18 at 22:12




            1




            1




            Since EV owners are likely to have guests with EVs and some EV chargers use a NEMA 6-50 whereas others evidently use a NEMA 14-50, the subpanel approach of @Harper would allow having a TESLA charger hardwired for the resident and would allow installation of both a NEMA 6-50R and a NEMA 14-50R to accommodate any EV charger. Although I gather there are adaptors to allow a NEMA 6-50P to connect to a NEMA 14-50R so all that is needed is a 14-50R.
            – Jim Stewart
            yesterday






            Since EV owners are likely to have guests with EVs and some EV chargers use a NEMA 6-50 whereas others evidently use a NEMA 14-50, the subpanel approach of @Harper would allow having a TESLA charger hardwired for the resident and would allow installation of both a NEMA 6-50R and a NEMA 14-50R to accommodate any EV charger. Although I gather there are adaptors to allow a NEMA 6-50P to connect to a NEMA 14-50R so all that is needed is a 14-50R.
            – Jim Stewart
            yesterday












            directedition is a new contributor. Be nice, and check out our Code of Conduct.










            draft saved

            draft discarded


















            directedition is a new contributor. Be nice, and check out our Code of Conduct.













            directedition is a new contributor. Be nice, and check out our Code of Conduct.












            directedition is a new contributor. Be nice, and check out our Code of Conduct.
















            Thanks for contributing an answer to Home Improvement Stack Exchange!


            • Please be sure to answer the question. Provide details and share your research!

            But avoid



            • Asking for help, clarification, or responding to other answers.

            • Making statements based on opinion; back them up with references or personal experience.


            To learn more, see our tips on writing great answers.





            Some of your past answers have not been well-received, and you're in danger of being blocked from answering.


            Please pay close attention to the following guidance:


            • Please be sure to answer the question. Provide details and share your research!

            But avoid



            • Asking for help, clarification, or responding to other answers.

            • Making statements based on opinion; back them up with references or personal experience.


            To learn more, see our tips on writing great answers.




            draft saved


            draft discarded














            StackExchange.ready(
            function () {
            StackExchange.openid.initPostLogin('.new-post-login', 'https%3a%2f%2fdiy.stackexchange.com%2fquestions%2f153571%2fswitch-for-alternating-between-outlets%23new-answer', 'question_page');
            }
            );

            Post as a guest















            Required, but never shown





















































            Required, but never shown














            Required, but never shown












            Required, but never shown







            Required, but never shown

































            Required, but never shown














            Required, but never shown












            Required, but never shown







            Required, but never shown







            Popular posts from this blog

            Сан-Квентин

            Алькесар

            Josef Freinademetz